Hitachi Energy urges upgrades over legacy RTU500 security flaws

The vendor says findings affect firmware 9.x and likely extend to end-of-life versions 11.x and earlier. It reports supported versions unaffected.

The vendor says findings affect firmware 9.x and likely extend to end-of-life versions 11.x and earlier. It reports supported versions unaffected.
Hitachi Energy is urging operators of legacy RTU500 systems to upgrade their firmware—the software built into the devices—because security flaws could allow unauthorized changes or disrupt operation. The company is the source of the advisory, which CISA republished verbatim on October 6, 2026, rather than providing a separate technical assessment.
The advisory was first publicly released on September 29. Hitachi Energy says the end-of-life firmware versions no longer receive security updates. The advisory identifies energy as the relevant critical-infrastructure sector and says RTU500 systems are deployed worldwide.
According to Hitachi Energy, the findings reported by Dragos concern RTU500 CMU firmware version 9.x. The affected-product list covers versions 11.x and earlier, but the company’s broader assessment describes those legacy versions as likely affected. Hitachi Energy says currently supported CMU firmware versions are unaffected by the reported findings.
Several flaws could allow attackers to change software or files without authentication, meaning they would not need to prove their identity to the device. The advisory lists six CVE identifiers, which distinguish individual vulnerabilities. Its CVSS 3.1 scores rate their technical severity; the effects below are Hitachi Energy’s descriptions of possible attacks.
| CVE identifier | Vendor score and severity | Potential effect |
|---|---|---|
| CVE-2026-8065 | 9.1 — Critical | Missing authentication in firmware updating could let an attacker upload arbitrary firmware, alter device functions, make unauthorized changes or prevent the device from operating. |
| CVE-2026-8066 | 9.1 — Critical | A flaw in how file uploads handle file locations could let an unauthenticated attacker write or overwrite arbitrary device files. Depending on the files affected, this could change data or disrupt operation. |
| CVE-2026-8067 | 6.5 — Medium | A flaw in the web application’s permission checks could let an authenticated user reboot the device, causing temporary unavailability and disrupting operation. |
| CVE-2010-2965 | 9.8 — Critical | A flaw in the Wind River VxWorks debugging service used by some legacy firmware versions could let remote attackers read or change device memory, call software functions or manage running tasks. |
| CVE-2014-9195 | 8.1 — High | Missing authentication in a network service could let an unauthenticated remote attacker run arbitrary commands, potentially modifying the device or disrupting operation. |
| CVE-2023-46143 | 7.5 — High | Downloading code without checking its integrity could let an unauthenticated remote attacker modify some or all running applications, potentially changing device functions or disrupting operation. |
Hitachi Energy has not said how many installations are affected or whether these flaws are being actively exploited.
Hitachi Energy recommends upgrading affected installations to firmware 12.7.8, 13.9.1 or the latest supported version. The recommendation applies to the legacy versions listed in the advisory, not just version 9.x.
Alongside upgrades, the company recommends layered safeguards: prevent direct internet connections to process-control systems, restrict physical access and separate control systems from other networks with firewalls that limit exposed network ports. These measures can help protect control networks from attacks originating outside them, Hitachi Energy says.
For further information and support, the advisory directs operators to their product provider or Hitachi Energy’s service organization.

The vendor says the flaws can disrupt service in versions 8.3.3.1 and earlier. Both require authenticated access; one also requires local access.