Grid Protection Alliance fixes openPDC and openHistorian flaws

Operators need updates and explicit checks of data-sharing settings. The published openPDC Docker image lacks key fixes.

Operators need updates and explicit checks of data-sharing settings. The published openPDC Docker image lacks key fixes.
Grid Protection Alliance has released fixes for openPDC and openHistorian, but installing an update alone does not close every exposure. In an October 8 advisory, the US Cybersecurity and Infrastructure Security Agency (CISA) warns of a critical flaw that could let a network attacker run code. Operators must also check whether data-sharing interfaces still accept connections from other computers.
The software is deployed in the energy sector worldwide. Earlier publisher settings allowed connections without authentication by default. The new defaults restrict those interfaces to the local computer, but existing installations retain their old settings when upgraded.
CISA lists openPDC versions before 2.9.482, including the published Docker image, and openHistorian versions before 2.8.585 as affected. The component-loading flaw received checks in earlier releases; the service-console fix arrived at the later thresholds below.
| Software | Service-console fix available from | Component-loading checks available from |
|---|---|---|
| openPDC | 2.9.482 | 2.9.477 |
| openHistorian | 2.8.585 | 2.8.580 |
The critical service-console flaw, CVE-2026-100730, concerns deserialization: rebuilding software objects from data sent by a client. CISA says this could allow remote code execution with the privileges of the service account—the account under which the software runs. It rates the flaw 9.8 out of 10 on the CVSS 3.1 severity scale.
On systems without Windows Authentication, a network attacker can reach this function without logging in. Where Windows Authentication is enabled, the attacker must already be authenticated. Grid Protection Alliance added validation to the serialization logic in openPDC 2.9.482 and openHistorian 2.8.585 and later versions.
Two other flaws affect openPDC’s data-sharing interfaces. The internal publisher can disclose the complete layout of the system’s devices and measurements without authentication (CVE-2026-105281). The STTP-based publisher, another data-sharing interface, allows an unauthenticated network attacker to exchange data with it (CVE-2026-85479).
For both products, the publisher fixes change the default binding—the network address on which an interface accepts connections—to the local loopback address. That limits connections to the same computer. The change applies only to new installations: operators upgrading an existing installation should explicitly check its bindings and change any that still accept connections on all interfaces.
The Modbus connection flaw in openPDC (CVE-2026-101022) requires an authenticated user. It allows connections to unrestricted internal network destinations, potentially revealing which computers are reachable and helping an attacker map the network. Grid Protection Alliance recommends firewall restrictions and blocking connections to loopback and private network addresses unless explicitly required.
The component-loading flaw in both products (CVE-2026-104629) requires an authenticated account and the ability to place a file on the host computer. It can then allow code to run with the service account’s privileges. The earlier fixes listed above add verification and integrity checks for adapters, the software components being loaded.
The published openPDC Docker image, a packaged version of the application, includes a fixed administrative credential with no required change on first use (CVE-2026-105278). CISA says an attacker who can reach its management interface can use that credential to gain full administrative control of the application.
The advisory lists “No fix planned” for the Docker image’s service-console, publisher-interface and fixed-credential vulnerabilities, and says those fixes have not been published to the image. Grid Protection Alliance recommends against production use of its published Docker images.
It is not yet clear whether the vulnerabilities have been exploited. For existing installations, the next protective steps are to apply the available software fixes, verify the publisher bindings separately and follow the vendor’s network restrictions for Modbus connections.

The company sells analytics based on public model comparisons and has added a preliminary alignment leaderboard.